فهرس المقالات Bahram Noshad


  • المقاله

    1 - A New Model for Analysis of Unusual Mal-Operation of Differential Protection Due to the Ultra-Saturation Phenomenon during the Loaded Power Transformer Energization
    Journal of Advances in Computer Research , العدد 4 , السنة 9 , تابستان 2018
    In this paper, a new model based on the thevenin equivalent circuit for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the transformer is considered. The u أکثر
    In this paper, a new model based on the thevenin equivalent circuit for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the transformer is considered. The ultra-saturation phenomenon causes the mal-operation of the power transformer differential protection. So, the description and control of the ultra-saturation phenomenon is necessary for preventing of the false trip of the differential protection. In this paper, to model the ultra-saturation phenomenon, the nonlinear characteristic of the transformer core, the effect of current transformer, and the core losses are taken into account. It is assumed that the load of the transformer is a resistive and inductive load. Also, the effect of the residual flux and inception angle on the ultra-saturation phenomenon are investigated. The results show that the ultra-saturation phenomenon poses a great problem for protective relaying of power transformers. The outcomes of this research can further be used as hints for substation operation personnel as well as for the development of new protection stabilization criteria, which is not discussed further in this paper. The explanation of the ultra-saturation phenomena is the first step toward developing new ideas and criteria for more reliable transformer protection that would better handle such abnormal cases than currently employed relaying equipment. In this paper, the fourth-order Runge-Kutta method is used to solve the equations and simulation of the ultra-saturation phenomenon is done by MATLAB program. تفاصيل المقالة

  • المقاله

    2 - Determination of a New Model to Study Ultra-Saturation Phenomenon During the Loaded Power Transformer Energization and its Effect on Differential
    Journal of Advances in Computer Research , العدد 1 , السنة 10 , زمستان 2019
    One of transient phenomenon that causes the mal-operation of the power transformer differential protection during the energization of a loaded power transformer is the ultra-saturation phenomenon. In this paper, a new model for investigating the ultra-saturation phenome أکثر
    One of transient phenomenon that causes the mal-operation of the power transformer differential protection during the energization of a loaded power transformer is the ultra-saturation phenomenon. In this paper, a new model for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the power transformer is considered. In this model, the nonlinear characteristic of the power transformer core, the effect of current transformers, and the core losses of the power transformer are taken into account. It is assumed that the load of the power transformer is a resistive and inductive load. Also, the effect of the residual flux and inception angle on the ultra-saturation phenomenon are investigated. In this paper, simulation is done by MATLAB software. The differential protection of the power transformer must be accurate and fast, so the description of the ultra-saturation phenomena is the first level for preventing of the mal-operation of the differential protection. The outcomes of this research can further be used as hints for substation operation personnel as well as for the development of new protection stabilization criteria, which is not discussed further in this paper. تفاصيل المقالة